根據《供熱通(tong)(tong)(tong)(tong)風(feng)(feng)設計手冊(ce)》規(gui)范GBJ19-87和《DB42實驗室(shi)通(tong)(tong)(tong)(tong)風(feng)(feng)系(xi)統設計與施工(gong)規(gui)范》的相關規(gui)定,確定通(tong)(tong)(tong)(tong)風(feng)(feng)柜、消(xiao)化柜、原子吸收(shou)罩等通(tong)(tong)(tong)(tong)風(feng)(feng)設備(bei)、室(shi)內全面通(tong)(tong)(tong)(tong)風(feng)(feng)換氣(qi)的通(tong)(tong)(tong)(tong)風(feng)(feng)量:
1) 設計(ji)中,按室內余熱、余濕、保證室內衛(wei)生條(tiao)件(jian)的最小換氣量(liang)進行計(ji)算。
一般性化學實驗室的通風量: 10-12次(ci)/小(xiao)時
毒氣室(shi)、有(you)機(ji)合成、菌種培養(yang)的通(tong)風量:15-20次/小時
2) 通(tong)風(feng)(feng)柜(ju)(ju)(罩)排(pai)風(feng)(feng)工作面必須保持(chi)負壓狀態,通(tong)風(feng)(feng)柜(ju)(ju)面風(feng)(feng)速:
VAV狀態 0.5m/s±0.1m/s或根據用戶要(yao)求設(she)定其它值。
手(shou)動狀態0.3m/s~1m/s,視窗的高低不影響面所設定風速;
3) 通風(feng)系統(tong)使用(yong)終端噪音≤55dB ,通風(feng)柜面換氣次數:不小于(yu)15次;
4) 主風(feng)管(guan)設(she)計風(feng)速小于9-12m/s,支風(feng)管(guan)設(she)計風(feng)速小于5-7m/s
5) 排風量:通風柜1500m3/h;
6) 快速執行器響應時間≤1s。
二、 補風機系統規定1) VAV變風量(liang)變頻調(diao)節(jie)控制,保(bao)證系統多個通風柜(ju)(罩)同時(shi)運行時(shi),各自獨立調(diao)節(jie),不相互干擾。
2) 實(shi)驗(yan)室(shi)內(nei)氣(qi)流(liu)組織良好,氣(qi)流(liu)速度及紊流(liu)度均能控制在(zai)較小的(de)(de)范圍內(nei),以免室(shi)內(nei)氣(qi)體的(de)(de)擾動引起排毒柜內(nei)氣(qi)體外溢(yi)。
3) 應有不同型號和規格(ge)的圓形(xing)或矩形(xing)單個變風(feng)量閥,滿(man)足(zu)不同風(feng)量要(yao)求并與設計圖紙相符合(he);
4) 結合實驗室(shi)排(pai)風(feng)控制系統,包括變風(feng)量閥、消音器等(deng)能提供實驗室(shi)通風(feng)控制的完整解決(jue)方案。
5) 實驗室風(feng)管在選(xuan)擇防(fang)腐(fu)蝕較(jiao)好,硬度高的材質。本工程涉及到所有(you)風(feng)管均可采用防(fang)腐(fu)蝕性(xing)能(neng)好的PVC/UPVC材質,風(feng)機(ji)全部(bu)為腐(fu)蝕性(xing)能(neng)好的玻璃鋼風(feng)機(ji)。
6) 控(kong)(kong)制面(mian)板為漢字顯示,可顯示通(tong)風系(xi)統運(yun)行(xing)時的多項信息。自動與手動多種工(gong)作(zuo)模式(shi)可兼容設定,控(kong)(kong)制插(cha)座電源及照明的開(kai)啟,可調節風閥角度(du)。
7) 實(shi)驗(yan)室內(nei)氣流組織良(liang)好,送回風氣流速(su)度(du)及紊流度(du)均(jun)能(neng)控制在(zai)較小的(de)范圍內(nei),以免室內(nei)氣體的(de)擾動引起排毒柜(ju)內(nei)氣體外(wai)溢。